Product name: Inverter ATV312
Manufacturer: Schneider
Contact rates
Condition: New 100%
Details
Schneider Altivar 312 inverter family is the inverter family developed by electric-schneider with powerful features with frequency range from 0 to 500Hz, capacity of 0.18 to 15Kw with many functions such as: Engine thermal protection function, function auto start function, auto start function according to loading speed, reversing function, braking function, remote control connection function …
Basic technical parameter
– Range of capacity from 0.18 to 15KW
– Single-phase input voltage 200 … 240V, 3-phase 200 … 600V
– 3-phase output voltage 200 … 600V
– Auto tuning function “auto tuning”
– Braking function
– Thermal protection function according to I2t formula.
– Integrated EMC filter
– Integrating Modbus, CANopen, Profibus DP, Device NET, Ethernet interfaces
– Integrated PID, +/- speed, controls up to 16 speed levels with 6 logic inputs
– Easy installation and operation, stable operation, meeting load for continuous operation, saving energy …
Factory default settings for the ATV312 inverter Altivar 31xx is installed by default for the most common operating conditions
– Display: BBT is ready (rdY) when the motor is stopped and the motor frequency when the engine is running.
– Motor frequency (bFr): 50Hz.
– The application maintains a fixed moment by controlling the magnetic flux vector, without the need for a sensor.
– Normal stop mode according to acceleration / deceleration (Stt = rMP).
– Stop mode when there is an error: free
– Acceleration / deceleration steps: linear acceleration / deceleration (ACC, dEC): 3 seconds.
– Low speed (LSP): 0Hz.
– High speed (HSP): 50Hz.
– Motor thermal current (ItH) = rated motor current (dependent on BBT capacity).
– Motor braking current (SdC) = 0.7x BBT nominal current, braking time of 0.5 seconds.
– Automatic adjustment of deceleration time in case of overvoltage during braking.
– Do not start automatically after an error.
– Inverter switching frequency: 4kHz.
– Logic inputs:
-
- LI1, LI2 (2-way operation): 2-wire control according to status, LI1 = forward, LI2 = invert. For ATV31xxxxxxA, these two inputs do not have a function
- LI3, LI4: used to select 4 preset speeds (speed 1 = reference speed or equal to 0, speed 2 = 10Hz, speed 3 = 15Hz, speed 4 = 20Hz).
- LI5-LI6: not yet assigned a function.
– Analog inputs:
– AI1: 0-10V speed reference, not yet assigned to ATV31xxxxxxA.
– AI2: Reference total speed 0 ± 10V.
– AI3: 4-20mA without assigning a function.
-
- Relay R1: open contact when faulty (or power off BBT).
- Relay R2: No function assigned.
- AOC analog output: 0-20mA without assigning a function.
Application