Description
Overview
– FR- CV fire retardant cable is designed to maintain electrical power for equipment, limiting the spread of flames when affected by a fire.
– Fire-retardant cables suitable for use in public works, backup electrical systems, emergency systems, fire alarms, sprinkler systems, smoke and smoke alarms, exit light systems insurance … rated voltage 0.6 / 1 kV, fixed installation.
Applied standard
– TCVN 5935-1 / IEC 60502-1.
– TCVN 6612 / IEC 60228.
– IEC 60332-1.3. IEC 60331-21.
Cable identification
Orange or as required.
Structure
Technical features
– Voltage level U0 / U: 0.6 / 1kV.
– Test voltage: 3.5kV (5 minutes).
-The permissible long-term working temperature for conductors is 70ºC.
– The maximum allowable temperature of the conductor when short-circuiting for no more than 5 seconds is:
– 140ºC, with an area larger than 300mm2.
– 160ºC, with a cross section less than or equal to 300mm2.
– Fire retardant wire has the characteristics of slow fire transmission so it is difficult to catch fire.
– The cord has the ability to turn itself off after removing the fire source.