CXV/AWA/FRT – 0,6/1KV & CXV/SWA/FRT – 0,6/1KV Flame Retardant Cables, Copper Conductor, XLPE Insulation Metallic Wires Armour, FR-PVC Sheath

Description

OVERVIEW

Fire resistant cables CXV / AWA (SWA) / FRT for power distribution systems are designed to limit the spread of flames when affected by a fire, used appropriately in buildings … voltage level 0.6 / 1 kV, fixed installation.

APPLIED STANDARD

– TCVN 5935-1 / IEC 60502-1
– TCVN 6612 / IEC 60228
– IEC 60332-1.3
– BS 4066-1.3

ACKNOWLEDGE ERROR

– By color tape:
+ Cable 1 core: Natural color, not colored tape.
+ Multi-core cable: Red – yellow – blue tape – no color tape.
– Or according to customer requirements.

CONSTRUCTION

5

TECHNICAL CHARACTERISTICS

– Voltage level U0 / U: 0.6 / 1 kV.
– Test voltage: 3.5 kV (5 minutes).
– Permissible long-term working temperature for conductors is 90°C.
– The maximum permissible temperature of the conductor when short-circuited for no more than 5 seconds is 250°C.
– Fire-retardant cable has characteristics of slow fire transmission so it is difficult to catch fire.
– The cable has the ability to turn itself off after removing the fire source.