CVV/AWA/FRT – 0,6/1KV & CVV/SWA/FRT – 0,6/1KV Flame Retardant Cables, Copper Conductor, PVC Insulation Metallic Wires Armour, FR-PVC Sheath

Description

GENERAL SCOPE

The flame retardant CVV/AWA (SWA)/FRT cables are designed to restrict the propagation of flames when affected by fire, they are proper used for public facilities…, rated voltage 0,6 /1 kV, fixed  wiring.

APPLIED STANDARD

– TCVN 5935-1 / IEC 60502-1
– TCVN 6612 / IEC 60228
– IEC 60332-1,3
– BS 4066-1,3

IDENTIFICATION OF CORES

– By color of insulation or by color stripe:
+   Single core cable: Black.
+   Multi-core cable: Red – yellow – blue – black.
– Or by customer’s requirement.

CONSTRUCTION

3

TECHNICAL CHARACTERISTICS

– Voltage level U0 / U: 0.6 / 1 kV.
– Test voltage: 3.5 kV (5 minutes).
– Permissible long-term working temperature for conductors is 70°C.
– The maximum allowable temperature of the conductor when short-circuiting for no more than 5 seconds is:
– 140°C, with an area larger than 300mm2.
– 160°C, with a section less than or equal to 300mm2.
– Fire-retardant cable has characteristics of slow fire transmission so it is difficult to catch fire.
– The cable has the ability to turn itself off after removing the fire source.