Description
OVERVIEW
Flame retardant CVV / DATA (DSTA) / FRT cables for power distribution systems are designed to limit the spread of flames when affected by a fire, used appropriately in buildings … voltage level 0.6 / 1 kV, fixed installation.
APPLIED STANDARD
– TCVN 5935-1 / IEC 60502-1
– TCVN 6612 / IEC 60228
– IEC 60332-1.3
– BS 4066-1.3
ACKNOWLEDGE ERROR
– By colored or colored stripes:
+ Cable 1 core: Black.
+ Multi-core cable: Red – yellow – blue – black.
– Or according to customer requirements.
CONSTRUCTION

TECHNICAL CHARACTERISTICS
– Rated voltage U0/U: 0,6/1 kV.
– Test voltage: 3,5 kV (5 minutes) .
– Maximum conductor temperature for normal operation is 70°C.
– Maximum conductor temperature for short-circuit (5s maximum duration) is:
– 140°C with Nominal area larger than 300mm2.
– 160°C with Nominal area up to and include 300mm2.
– Cables are subjected to fire at 950°C for 3 hours.
– The cables pass BS 6387 Cat. CWZ.
– The fire resistant cables have a significant reduced tendency to propagate fire.
– The cables must self-extinguish after removing the fire source