INVERTER SV220IP5A-4

INVERTER SV220IP5A-4

SKU: 110-bien-tan-sv220ip5a-4 Category:

Description

Technical characteristics

– Input voltage: 3 phase 380-480 V, 50-60 Hz
– Output voltage: 3 phase 380-480 V, 0-120 Hz
– Capacity: 22 KW
– Variable torque for HVAC and pump
– Controlless vector control and V / f
– 150% torque throughout the range
– Automatically detects engine parameters (auto-tuning)
– 32 bit high speed digital signal processor
– Bearing frequency 0.7 ~ 15kHz
– Integrated multi-motor control (up to 4)
– Integrated PID control method
– Up / Down and 3-wire operation function
– Integrated Mudbus communication (RS485)
– Analog inputs: 0 ~ 10VDC, -10 ~ + 10VDC
– Dynamic input (NTC / PTC)
– Optional sud-boards, ProfuBus and DeviceNet
– Brake unit options
– Cooling fan control On / Off (with type above 37kW)

Technical data

Control method V / F control, sensorless vector
Set frequency resolution Digital reference: 0.01Hz (below 99Hz) and 0.1Hz (≥100Hz) Analog reference: 0.06Hz at 60Hz
Accuracy frequency set Digital: 0.01% of maximum output frequency Analog: 0.1% of maximum output frequency
V / F ratio Linear, square, use V / F
Ability to overload 110% for 1 minute, 150% for 4 seconds (inversely proportional to time)
Starting torque Automatic, manual (0 ~ 15%)
Multi-function input Total 8 inputs (Programmable)
Analog output 0 ~ 10V linear
Signal input Operation control 32-character LCD key, 4-digit LED, output connector, Modbus-RTU communication
Optional Modbus-RTU, RS485, ProfiBus-DP, DeviceNet, F-Net
Frequency set Analog: 0 ~ 10V, 0 (4) ~ 20mA, Sub-Board auxiliary port (0 ~ 10V) Digital: Keypad

The media

Start signal Pros, reverse
Multi-level work Set up to 16 speed levels (using multifunction output)
Multiple levels of acceleration / deceleration time 0.1 ~ 6000 seconds. Preset up to 8 levels for multi-function output
The operation function 1-way braking, frequency limiting, hopping frequency, 2nd motor function, slip compensation
Reverse prevention, auto restart, inverter by-pass, auto-tuning, PID control
Emergency use Output from the inverter
Jog Operation does not load
fault reset Reset the error signal when the protection function operates
Output signal Operation status Frequency detection, overload error, isolation (stall), over voltage, under pressure, overheat inverter, run, stop, constant speed
Detect speed, output error (relay output and open collector), inverter by-pass, auto-level operation, automatic continuous operation
Directive Frequency output, current output, voltage output, DC voltage, torque output (output voltage: 0 ~ 10V)
The protection function Trip (release) Over voltage, under voltage, over current, overheat inverter, motor overheat, I / O phase loss, I / O wire breakage, open fuse
Earthing, external input error (external 1,2), fault selection, overload, loss of speed control command, hardware error, communication error
Error Stall, overload, heat sensor error