Description
Technical data
Dimensions: 159mm (6.26 “) × 177mm (6.97”) × 53 mm (2.09 “)
Weight: 610 g (6.5oz)
Measure insulation resistance
– Output voltage: 250V DC, 500V DC, 1000V DC
– Maximum measurement value: 100MΩ, 4000 MΩ
– Central scale value: 1.0MΩ, 50MΩ
– First measurement range: 0.05 – 50MΩ, 2 – 1000 MΩ, ± 5% of measured value
– Second measurement range: 0.01 – 0.05MΩ 50 – 100MΩ, 0.5 – 2 MΩ 1000 – 4000MΩ, ± 10% of measured value
– Open voltage current: 1 to 1.2 times of the output voltage norm
– Lowest resistance measurement limit value: 0.25 MΩ, 0.5 MΩ, 1 MΩ
– Ampere current: 1mA (Tolerance: 1 to 1.2 times the measured value)
– Safe load: 1200V AC (10 sec.)
Resistance measurement
– Measuring range: 3Ω, 30Ω
– Central scale value: 1.5Ω, 15Ω
– Accuracy: ± 0.09 Ω, ± 0.9 Ω
– Open voltage current: 4.1 – 6.9V
– Measure ampere: 200mA DC or higher, 20mA DC or higher
– Safe load: 720V AC (10 seconds)
Measure ac voltage
– Measuring range: 0 – 600 V (50/60 Hz)
– Accuracy: ± 5% of the maximum scale value
– Input resistance: 100 kΩ or higher (50 / 60Hz)
– Safe load: 1200V AC (10 seconds)
Source: 1.5 VDC × 4 battery, LR6 alkaline × 4